Guardian K81D Hydrants
Dual Rated AWWA and UL/FM
Suggested Specifications
-
Hydrants shall be UL listed and FM approved.
-
Hydrants shall conform to AWWA Standard C-502 latest revision.
-
Hydrants shall be of the compression type, closing with line pressure.
-
Hydrants shall be of the traffic model breakaway type.
-
Hydrant cap and stuffing box shall be of a utilized, one piece design
creating a water tight cavity without the use of gaskets. The combination
of O-rings to a crimped brass ferrule around the stem shall seal the cavity
from contact with water. An alemite fitting shall be supplied for periodic
lubrication of the operating threads with grease.
-
Operating nut shall be of one piece bronze construction.
-
A dirt shield shall be provided to protect the operating mechanism from
grit buildup and corrosion due to moisture.
-
A thrust washer shall be supplied between the operating nut and stem
lock nut to facilitate operation.
-
Nozzles shall be of the tamper resistant, 1/4 turn type with O-ring
seals and stainless steel retaining screws.
-
An O-ring shall be provided to seal between the upper and lower barrels.
-
The main valve shall be of synthetic rubber reinforced with steel.
-
The seat shall be of a bronze ring threaded to a bronze insert in the
hydrant shoe, with O-rings to seal the drainway and barrel from leakage
of water in the shoe.
-
Hydrant drain valve shall momentarily force flush with each operation.
Drainway shall be of bronze. Drain valve facing shall be of synthetic rubber
with a stainless steel retaining pin.
-
Hydrants shall be Guardian as maunfactured by Kennedy Valve or approved
equal.